TH2 level control relay Toscano Adajusa
TH2 level control relay Toscano Adajusa

Dual control relay TH2-230/400 for water level - Toscano

€65.47 Tax included

€54.11 tax excl.

Double liquid (water) level control relay. It allows with a single relay the control of the well and the tank. This relay allows the connection of 4 probes (conductive), for maximum and minimum. Plug-in undecal base (11 pins). Operating voltage 230/400Vac.

Reference: TH2-230/400

Toscano_version 1 color sin leyenda
Representative image for illustrative purposes, the item supplied will correspond to the specifications indicated.

No queries yet, leave the first!
 

Fluid (water) level control relay of probes by conductive system. This level control relay allows double control, i.e. it controls the well level and the reservoir level simultaneously. Adjustable sensitivity and dual voltage operation, the same relay can operate at 230Vac or 400Vac.

The connection is made through an undecal base (not included in the supply), this facilitates assembly and subsequent maintenance.

By having a sensitivity control, this relay is suitable for situations where there are particular circumstances (high humidity, considerable distance between probes and equipment, ground capacity of the probe cable), in these cases, it is necessary to be able to reduce the sensitivity to avoid false activations of the relay.

It has a connection for 4 probes, two for the tank (maximum and minimum) and two for the well (maximum and minimum). The relay has a switched output count (NA/NC).

Connection:

Conexionado hidronivel TH2 toscano adajusa
Note: The supply does not include either the probes or the undecal base, only the relay.

Technical specifications:

  • Manufacturer: Toscano
  • Reference: TH2-230/400
  • Working voltage: 230/400 Vac 50Hz
  • Power consumption: 2 VA
  • Voltage tolerance: +10%-20%
  • Response Sensitivity: Adjustable 30..90 kΩ
  • Probe voltage: 12 Vac 50 Hz
  • Probe intensity: 1.2 mA maximum in short circuit
  • Maximum terminal section: 2x2,5mm²
  • Outgoing contact
    • AC1: 10A - 250Vac
    • AC11: 2.5A - 230Vac
    • DC1: 1A -250Vdc
    • DC11: 5A-24Vdc
  • Environmental margins -10º to +60ºC
  • Recommended maximum distance between relay and probes: approximately 150m

To expand the information, you can download the data sheet by clicking on the "Attachments" tab.
Material for professional use, must be installed by qualified personnel respecting the regulations in force at the site of installation.

Questions

Be the first to ask a question about this product!

Question about the product

* Required fields
(read)